Fault location on the high voltage series compensated power transmission networks

Kapuduwage, S 2006, Fault location on the high voltage series compensated power transmission networks, PhD Thesis, School of Electrical and Computer Engineering, RMIT University.

Document type: Thesis
Collection: Theses
Attached Files
Name Description MIMEType Size Downloads
Kapuduwage.pdf Thesis application/pdf 4.53MB 1556

Title Fault location on the high voltage series compensated power transmission networks
Author(s) Kapuduwage, S
Year 2006
Abstract Nowadays power transmission networks are capable of delivering contracted power from any supplier to any consumer over a large geographic area under market control, and thus transmission lines are incorporated with FACTs series compensated devices to increase the power transfer capability with improvement to system integrity.

Conventional fault location methods developed in the past many years are not suitable for FACTs transmission networks. The obvious reason is that FACTs devices in transmission networks introduce non-linearity in the system and hence linear fault detection methods are no longer valid. Therefore, it is still a matter of research to investigate developing new fault detection techniques to cater for modern transmission network configurations and solve implementation issues maintaining required accuracy.

This PhD research work is based on developing an accurate and robust new fault location algorithm for series compensated high voltage transmission lines, considering many issues such as transmission line models, configurations with series compensation features. Building on the existing knowledge, a new algorithm has been developed for the estimation of fault location using the time domain approach. In this algorithm, instantaneous fault signals from the transmission line ends are measured and applied to the algorithm to calculate the distance to fault. The new algorithm was tested on two port transmission line model developed using EMTP/ATP software and measured fault data from the simulations are exported to the MATLAB space to run the algorithm. Broad range of faults has been simulated considering various fault cases to test the algorithm and statistical results obtained. It was observed that the accuracy of location of fault on series compensated transmission line using this algorithm is in the range from 99.7 % to 99.9% in 90% of fault cases.

In addition, this algorithm was further improved considering many practical issues related to modern series compensated transmission lines (with TCSC var compensators) achieving similar accuracies in the estimation of fault location.
Degree PhD Thesis
Institution RMIT University
School, Department or Centre School of Electrical and Computer Engineering
Keyword(s) Electric power distribution--High tension--Reliability
Fault location
series compensation
instantaneous values
transmission lines
metal oxide varistor
MATLAB
EMTP
algorithm
 
Versions
Version Filter Type
Access Statistics: 240 Abstract Views, 1557 File Downloads  -  Detailed Statistics
Created: Mon, 21 Feb 2011, 08:05:59 EST by Sue Fraumano